With integrated auxiliary switch |
False |
With integrated under voltage release |
False |
Rated short-circuit breaking capacity lcu at 400 V, AC |
65 kA |
Rated operation power at AC-3, 400 V |
22 kw |
Rated permanent current Iu |
45 A |
Rated operation power at AC-3, 230 V |
13 kw |
Rated operating voltage |
230 A |
Type of control element |
Turn button |
Overload release current setting |
32 A |
Type of electrical connection of main circuit |
Screw connection |
Magnetic release current per IEC |
585 A |
Magnetic trip current, nom |
585 A |
Rated operational current (Ie) per IEC |
45 A |
Rated supply current (Ie) |
6.3 A |
Short circuit current (Icu) for group motor installation, max |
65kA @ 480V |
Short circuit current (Type 2 coordination) with 100-C IEC contactor, max |
65kA @ 480V |
Current range |
32…45 A |
Ultimate short circuit breaking capacity (Icu) per IEC |
65kA @ 400/415V AC |
Rated service short circuit breaking capacity (Ics) per IEC |
6kA @ 690V AC |
Insulation voltage (Ui) |
Rated 690V per IEC |
Hp rating, max |
40Hp @ 575V, 3-phase |
Electrical life cycle |
30000 ops (Ie maximum) |
Short circuit current for self-protected combination motor controller with 100-C contactor, max |
65 kA @ 480Y/277V, UL 508-Type E |
Switching of standard motors per IEC |
40 kW @ 690V (AC-3), 3-phase |
KW rating, max |
40 kW @ 690V (AC-3), 3-phase |
Back up fuse (gG, gL) current rating (if Icc ≥ Icu ) per IEC |
No back-up fuse required @ 230/240V AC |
Short circuit current for combination motor controller with 100-C IEC contactor, max |
65 kA @ 480Y/277V, UL 60947-4-1-Type F |
Total power loss (Pv) for circuit breaker |
7…22 W @ rated load/operating temperature |
Short circuit current for group motor installation with 100-C IEC contactor, max |
65kA @ 480V, UL 60947-4-1-manual motor controller |
Short circuit current for motor disconnect with 100-C IEC contactor, max |
65kA @ 480V, UL 60947-4-1-manual motor controller |
Rated thermal current (Ith) |
6.3…45 A up to 60 °C (140 °F) ambient temperature |
Short circuit current for tap conductor protection, max |
65 kA @ 480Y/277V, UL 60947-4-1-manual motor controller |
Short circuit current for combination motor controller, max |
65kA @ 480V/277V, UL 60947-4-1 self-protected (Type E) |
Fuse or circuit breaker per NEC, max |
600 A, UL 60947-4-1-manual motor controller |
Rated impulse withstand voltage (Uimp) |
Main circuits (Uimp)/overvoltage category: 6 kV/III, 8 kV (disconnect) |
Short circuit current for group motor installation, max |
65kA @ 480V, UL 60947-4-1-manual motor controller |
Short circuit current for motor disconnect, max |
65kA @ 480V, UL 60947-4-1-manual motor controller |
Number of poles |
3 |
With thermal protection |
True |
Phase failure sensitive |
True |
Switch off technique |
Thermomagnetic |
Switching frequency, max |
25 ops/h |
Trip class |
10 |
Rated frequency |
45 Hz |
Phase loss protection |
Differential release |
Fuse or circuit breaker rating with 100-C IEC contactor per NEC, max |
600 A, UL 60947-4-1-manual motor controller |
There are no reviews yet.