Voltage type for actuating |
AC/DC |
Rated control supply voltage at AC 50 Hz |
250 V |
Rated control supply voltage at AC 60 Hz |
250 V |
Rated control supply voltage at DC |
250 V |
Type of electrical connection of main circuit |
Screw connection |
Rated impulse voltage withstand (Uimp) |
6 kV |
Operating time, closing delay |
40 ms |
Optional overload relays |
Electronic |
Main current circuit resistance |
0.41 mΩ |
Rated isolation voltage (Ui) |
690V per IEC |
Function |
Non-reversing contactor |
Standard coil, pick-up |
50VA/50 W @ 250…500V AC/DC |
Standard coil, hold-in |
2.2VA/2 W @ 250…500V AC/DC |
General purpose current (enclosed) |
13.8A @ 600V per UL/CSA |
Power dissipation |
0.8 W per pole at Ie, AC-1, 400V |
Short time withstand (Icw) |
3-pole: 80A @ 30s (40 °C) |
FLA |
20A @ 600V, 3-phase per UL/CSA HVAC applications |
Rated operational current and power (enclosed) |
9.5A @ 125V DC, with 3-poles in series per UL/CSA |
LRA |
80 A @ 550-600V, 3-phase AC per UL/CSA HVAC applications |
Electromagnetic compatibility |
IEC 60947-1 – Environment A and B (100-E09…E38 only) |
Total power dissipation |
2.3 W at Ie, AC-3, 400V, AC/DC control (120-250V) |
Operating limits, dropout |
(≤0.60) x Us @ DC control |
Rating for switching AC motors |
3-poles: 7.5Hp @ 575V, AC-2, AC-3 (60 Hz) |
Operating limits, pick-up |
(0.85…1.1) x Us @ 50/60 Hz |
MCCB current rating |
Type 2 (per IEC 60947-4-1): 28A @ 400V, 70 kA available fault current |
DIN fuses (gG) current rating |
Type 2 (per IEC 60947-4-1): 6A @ 690V, 60 kA available fault current |
Rated voltage (Ue) |
24, 48, 110, 220, 440V DC |
Rated operational current and power |
5.8A @ 115V AC, 500000 electrical ops, 1-phase per UL/CSA elevator duty |
Coil voltage |
250 to 500V AC/DC |
Switching of lighting loads |
Tungsten lA: 20A @ 600V, 3-phase (break all lines) per UL/CSA |
UL class RK5 fuses rating |
Type 1 Combination (per UL 60947 and CSA 22.2 No. 14): 30A @ 600V, 5 kA available fault current |
Rated operational current (Ie) |
9.5A @ 500V, Star-Delta starting (50 Hz) |
UL class J and CSA HRCI-J fuses rating |
Type 1 Combination (per UL 60947 and CSA 22.2 No. 14): 30A @ 600V, 100 kA available fault current |
UL inverse-time circuit breaker |
Type 1 Combination (per UL 60947 and CSA 22.2 No. 14): 60A @ 600V, 5 kA available fault current |
Switching of power transformers |
Apparent power: 8 kVA @ 415V, AC-6a @ 50Hz (n = 30) |
Rated operational power (Pe) |
9 kW @ 240V, AC-1 active power load (50/60 Hz), ambient temperature 70 °C (158 °F) |
Switching of DC loads |
3-poles in series: 9A @ 220V (Series-wound motors-starting, reverse current breaking, reversing, stepping: DC-5 at 60 °C) |
Optional accessories |
Side-or front-mount auxiliary contacts, Mechanical interlocks, Connecting bars |
Features |
Panel mounting or mounting on 35 mm DIN rail, AC/DC electronic coil, Made of environmentally friendly materials |
There are no reviews yet.