Unity processor, Modicon Quantum automation platform, Modbus Plus, 548kB RAM, 66MHz
140CPU31110
Range of Product | Modicon Quantum automation platform |
---|---|
Product or Component Type | Unity processor |
Clock frequency | 66 MHz |
---|---|
Number of slots | 16 4 10 2 6 |
Number of racks | 2 – local |
Number of distributed I/O station | 63 1 3 Modbus Plus |
Number of remote I/O station | 31 – 2 S908 remote I/O 0 – 0 ethernet remote I/O |
Discrete I/O number | Unlimited (27 slots max) – local 31744 inputs, 31744 outputs – remote 8000 inputs, 8000 outputs – distributed – per network Modbus Plus |
Analogue I/O number | Unlimited (27 slots max) – local 500 inputs, 500 outputs – distributed – per network Modbus Plus 1984 inputs,1984 outputs – S908 remote I/O |
Application specific I/O | High-speed interrupt inputs Counter Accurate time stamping Serial link |
Number of optional modules | 2 Ethernet, Modbus, Modbus Plus, Profibus DP, Sy/Max) |
Maximum number of connections | 1 USB 2 AS-Interface – distributed 2 Ethernet TCP/IP – local 2 Modbus Plus – local 2 Modbus RS232/485 Modbus/ASCII) 2 Profibus DP – local 4 AS-Interface – remote |
Integrated connection type | 1 Modbus Plus 2 Modbus |
Checks | Process control |
Memory description | Internal RAM 548 kB |
Switch Function | Slide switch communication port : ASCII/RTU/Memory Slide switch memory port/off |
Application structure | 1 cyclic/periodic master task – 1 periodic fast task – 16 timer interrupt tasks – 64 I/O interrupt tasks – 64 interrupt tasks – No auxiliary task – |
Execution time per instruction | 0.1…0.27 µs floating points 0.1…0.27 µs on fixed-point arithmetic 0.12…0.585 µs Boolean 0.12…0.585 µs on word |
Number of instructions per ms | 1.86 Kinst/ms 100 % Boolean 2.49 Kinst/ms 65 % Boolean and 35 % numerical |
System overhead | 0.2 ms fast task 1 ms master task |
Bus current requirement | 1800 mA |
Local signalling | for communications are active on the Modbus Plus port (Modbus Plus) 1 LED (green) for communications are active on the Modbus port (Modbus) 1 LED (green) for CPU has been started and is solving logic (RUN) 1 LED (green) for CPU has passed the power-up diagnostic tests (READY) 1 LED (green) for write-protected memory (memory port) 1 LED (orange) for battery needs replacing or is not present (BAT LOW) 1 LED (red) for communications error on the Modbus Plus port (ERROR A) 1 LED (red) |
Electrical connection | 1 female connector SUB-D 9 for connecting to the Modbus Plus network 2 female connectors SUB-D 9 for connecting to the Modbus bus |
Product Certifications | CSA CE UL |
---|---|
Standards | HazLoc |
Category | US1PC2118150 |
---|---|
Discount Schedule | PC21 |
GTIN | 3595862067300 |
Returnability | No |
Country of origin | FR |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 2.0 in (5.0 cm) |
Package 1 Width | 6.7 in (17.0 cm) |
Package 1 Length | 12.2 in (31.0 cm) |
Package 1 Weight | 25.4 oz (720.0 g) |
Warranty | 18 months |
---|
There are no reviews yet.